We’ve
all experienced water hammer at home: The shower valve is abruptly closed, or
the sprinkler system valve closes at the end of the cycle, or the washing
machine fill cycle ends and bam, all the pipes in the house rattle. What’s
happening? Any time you have a high-flow velocity, particularly in a long pipe
run, and there is a sudden change in velocity, water hammer can
occur.
The resulting pressure wave is transmitted throughout the system, subjecting
every component in the system to pressures approaching 10 times the normal
system pressure. The pressure returns to normal only when it is dissipated by
friction loss, pipe expansion or when something gives – a valve or section of
pipe. Let’s take a closer look at the causes of water hammer and consider some
remedies.
For water hammer to occur, four conditions must be present – sufficient flow
velocity, an abrupt change in velocity, a sufficiently long pipe run, and a
rigid piping system. Regarding the first condition – flow velocity – it
generally is agreed that water flow velocities below 5 feet per second (fps)
preclude the possibility of water hammer. The abrupt change in velocity can be
either rapid acceleration (pump start/valve opening) or rapid deceleration
(pump stop/valve closure). To quantify these changes in velocity, we use the
term, “critical time factor.”
This first formula below is used to calculate the critical time factor, the
velocity change timeframe below which water hammer occurs, based on the length
of the pipe run. The second formula offers a means for calculating the maximum
pressure surge resulting from water hammer in a rigid piping
system.
The formula used to calculate the critical time factor, which is the minimum
time duration for a valve to open or close or for a pump to start or stop
without causing water hammer, is as follows:
Critical Time Factor in seconds: Tc = 2L/S
Where: L = length of pipe in feet
S = Speed of sound in water (4,860
fps)
For example, if we have a 400-foot pipe run from the well to the house the
critical time factor would be:
Tc = 2 X 400 / 4,860
Tc = 0.16 seconds.
This means that if the pump takes less than 0.16 seconds to start, or if a
valve in the house is closed in less than 0.16 seconds, your pressure tank
better be in good working order. The pressure tank acts like a shock absorber,
and normally will absorb the shock wave. However, if it is waterlogged, you may
have a water hammer every time the pump starts or a valve is
closed.
What, then, would be the worst-case peak pressure caused from water hammer? The
Instrument Society of America (ISA) suggests the following formula for a rigid
piping system based on the assumption that the shock wave will travel at the
speed of sound, 4,860 fps for water. Of course, no piping system is absolutely
rigid, so the actual peak pressure would be a little less than these numbers.
Formula: Ps = Po + (64V X SG)
Where: Ps = Maximum pressure surge in
PSIG
Po = Normal system operating pressure in
PSIG
V = Velocity of fluid in FPS
SG = Specific gravity of fluid (1 for
water)
Let’s assume a 30/50 pressure switch, 20 gpm in 1-inch schedule 80 pipe. The
velocity of 20 gpm in 1-inch schedule 80 pipe would be about 7.5 fps. This
information is in the pressure loss charts available from most pipe and pump
manufacturers.
Therefore, the maximum pressure surge would be:
Ps = 50 + (64 X 7.5 X 1) = 537.5 psig
Now that we know how to calculate the severity of the water hammer problem, how
can we protect our system? Start with a good system design. Size the piping
such that the velocity does not exceed 5 fps. In the above example, if
11⁄4-inch pipe had been used instead of 1-inch, the velocity at 20 gpm would
have been on the order of 4 fps vs. 7.5 fps, and water hammer would not have
been an issue.
Also, make sure the pressure tank is checked regularly, and at the first sign
of air loss, fix the problem or replace the tank. Make sure there is not a
check valve between the house and the pressure tank. You want any shock waves
generated in the house to expand into the pressure tank, and a check valve
would prevent that from happening. The check valve needs to be between the
pressure tank and the pump.
Consider using a flow control valve to reduce the peak flow velocity to below 5
fps. Consider installing a stand pipe or small surge tank near the source of
the water hammer. Consider replacing quarter-turn ball valves with gate valves,
which open more slowly, or train the ball valve users to open and close them
slowly.
In an existing residential system, it often is possible to fix a water hammer
situation simply by shutting off the pressure to the house and opening the
lowest drain valve in the system to drain out some of the water in the pipes.
When houses are plumbed, it is standard practice to extend the piping inside
the walls a foot or so above each valve so that a pocket of air is trapped
above the valve to act as a water hammer shock absorber. Over time, the air
pocket will be absorbed into the water, and water hammer begins to occur.
Draining some of the water from the piping system refreshes these air pockets,
and water hammer is eliminated. Try it.
In larger systems, pilot-operated flow and pressure control valves can control the rate at which the velocity changes, be it on the pump
end or in the distribution system. Electronic soft-starts and variable-speed
drives are another good solution to water hammer caused by
pumps because they can be programmed to slowly ramp up and ramp down the pump
speed.
Whether it be a small residential water system or large commercial piping
system, water hammer can be a major problem. With an understanding of the
factors contributing to the problem and access to the necessary tools, it is
possible to tame this insidious gremlin and provide your customer with a quiet,
long-lasting pumped water system.
Next month, we will begin a three-part series on variable-speed drives. ’Til
then ….
ND
Tech Topics: All about Water Hammer
Looking for a reprint of this article?
From high-res PDFs to custom plaques, order your copy today!